EAST EA900 6-10kVA UPS (6 kVA – 10 kVA) EAST
EAST EAST Online EA900 6-10kVA

EAST EA900 6-10kVA UPS (6 kVA – 10 kVA)

The EAST EA900 G4A 6-10kVA (Online, tower) series is a single-phase online double-conversion UPS rated at 6 and 10 kVA with unity (1.0) output power factor, operating with DSP control and 3-level technology.
Technology
Online (Double Conversion)
Capacity
6–10 kVA
Phase
1-phase in / 1-phase out
  • On-line double conversion with DSP control and 3-level technology
  • Output power factor 1.0, input power factor up to 0.99
  • System efficiency up to 95%, up to 98% in ECO mode
  • Ultra wide input voltage range and 40 ~ 70 Hz frequency range
  • Flexible battery quantity configuration and intelligent charge management
  • Parallel up to 4 units
  • LCD + LED display; RS232 standard with optional SNMP, RS485, dry contacts
Price
Request a quote
In stock
Ask on WhatsApp 02128426849
Notify me of a price drop
Security code
Or order via messenger

Your order text is prepared and copied — just send it.

Genuine product After-sales service Nationwide delivery
Share:

Overview EAST EA900 6-10kVA UPS (6 kVA – 10 kVA)

The EAST EA900 G4A 6-10kVA (Online, tower) series is a single-phase online double-conversion UPS rated at 6 and 10 kVA with unity (1.0) output power factor, operating with DSP control and 3-level technology. Efficiency is ≥94% at full load and ≥98% in ECO mode, transfer time is zero, and up to 4 units can be paralleled. The series is offered in two versions, standard (internal batteries) and long backup (external batteries with a charger of up to 12 A), and is suitable for servers, network equipment, laboratories and medical equipment.

Key Features of the EA900 6-10kVA Series

  • Online double-conversion technology with DSP control and 3-level technology
  • Output power factor 1.0 and input power factor up to 0.99
  • System efficiency up to 95%, and up to 98% in ECO mode
  • Very wide input voltage range and 40 to 70 Hz frequency range
  • Flexible battery quantity configuration and intelligent charge management
  • Parallel capability for up to 4 units
  • LCD + LED display and standard RS232 communication, with SNMP, RS485 and dry contact options

Models in This Series

EA906, EA9010

Technical specifications are based on the manufacturer's (EAST) official datasheet and may vary depending on product version and generation.

Purchase and Consultation

Ista Afagh Energy supplies this series together with capacity-selection consulting, battery sizing for the required backup time, installation and commissioning, and after-sales service. For current pricing and stock availability, add the product to your order basket or contact us.

Technical specifications

BrandEAST
SeriesEA900 6-10kVA
Model
ModelsEA906, EA9010 (S = standard model, H = long time model)
CapacityEA906: 6kVA / 6kW | EA9010: 10kVA / 10kW
Input
Input wiringSingle-phase three-wire (1Φ + N + PE)
Rated voltage208 / 220 / 230 / 240Vac
Input voltage range176~288Vac (full load); 90~176Vac (linear derating to 30%)
Rated frequency50/60Hz
Frequency range40 ~ 70 Hz
Power factor≥ 0.99
Bypass voltage range- 40% ~ +15% (settable)
Input current THDi≤ 5%
Output
Output wiringSingle-phase three-wire (1Φ + N + PE)
Output voltage208 (PF=0.9) / 220 / 230 / 240 Vac
Voltage regulation± 1%
Output frequencySynchronized with utility in mains mode; 50/60Hz±0.1% in battery mode
WaveformSinusoidal
Output power factor1
Output voltage THDv<1% (full linear load); <4% (full non-linear load according to IEC/EN62040-3)
Crest factor3:1
Overload105% ~ 110% for 10 min, 110% ~ 125% for 1 min, 126% ~ 150% for 30 s
Transfer time0 ms
ProtectionsShort-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure
Max. parallel connections4
Battery
Battery DC voltageDefault 192Vdc (120~264Vdc)
Number of batteriesDefault 16pcs, settable 10-22pcs (10~15pcs linear derating to 50%)
Inbuilt battery (standard model)EA906: 12 V / 7 Ah × 16 | EA9010: 12 V / 9 Ah × 16
Charging currentStandard model: 1A (default), 1 ~ 5A settable; Long time model: 5 A (default), 1 ~ 5 A settable; 12 A (optional)
Recharge timeStandard model: 90% capacity restored in 8 hours; Long time model: depend on the capacity of battery
Efficiency
Efficiency≥ 94% at 100% load, max. 95% at 60% load, ≥ 98% in ECO mode
Display & Communication
DisplayLCD + LED
CommunicationsStandard: RS232, EPO, Smart card slot; Optional: SNMP card, Wi-Fi card, 4G card and SMS alarms, dry contacts, parallel kit, RS485
Operating Environment
Operating temperature0℃ ~ 40℃
Storage temperature-25℃ ~ 55℃ (without battery)
Relative humidity0 ~ 95% (non-condensing)
Altitude<1000m, derating 1% per 100m from 1000~2000m
IP ratingIP 20
Noise level (at 1 m)<58 dB
Dimensions & Weight
Dimensions (W×D×H) mm191×500×515 (S), 191×440×350 (H)
Packaged dimensions (W×D×H) mm310×654×600 (S), 318×570×475 (H)
Net weight (kg)EA906: 49.5(S), 14.5(H) | EA9010: 58.5(S), 15.5(H)
Gross weight (kg)EA906: 58(S), 16(H) | EA9010: 67(S), 17(H)

Catalogs & files