EAST EA900RT 6-10kVA UPS (6 kVA – 10 kVA) EAST
EAST EAST Online EA900RT 6-10kVA

EAST EA900RT 6-10kVA UPS (6 kVA – 10 kVA)

The EAST EA900RT G4A 6-10kVA (Online, rack/tower) series is a single-phase online double-conversion UPS rated at 6 and 10 kVA with unity (1.0) output power factor, operating with DSP control and 3-level technology.
Technology
Online (Double Conversion)
Capacity
6–10 kVA
Phase
1-phase in / 1-phase out
  • On-line double conversion with DSP control and 3-level technology
  • Rack/tower design with hot-swappable battery
  • Output power factor 1.0, input power factor up to 0.99
  • System efficiency up to 95%, up to 98% in ECO mode
  • Ultra wide input voltage range and 40 ~ 70 Hz frequency range
  • Flexible battery quantity configuration and intelligent charge management
  • Parallel up to 4 units
  • LCD + LED display; RS232 standard with optional SNMP, RS485, dry contacts
Price
Request a quote
In stock
Ask on WhatsApp 02128426849
Notify me of a price drop
Security code
Or order via messenger

Your order text is prepared and copied — just send it.

Genuine product After-sales service Nationwide delivery
Share:

Overview EAST EA900RT 6-10kVA UPS (6 kVA – 10 kVA)

The EAST EA900RT G4A 6-10kVA (Online, rack/tower) series is a single-phase online double-conversion UPS rated at 6 and 10 kVA with unity (1.0) output power factor, operating with DSP control and 3-level technology. Efficiency is ≥94% at full load and ≥98% in ECO mode, transfer time is zero, and up to 4 units can be paralleled. Its rack/tower design suits installation in server room racks and data centers, and it is offered in two versions, standard (internal batteries) and long backup (external batteries).

Key Features of the EA900RT 6-10kVA Series

  • Online double-conversion technology with DSP control and 3-level technology
  • Rack/tower design and hot-swappable batteries
  • Output power factor 1.0 and input power factor up to 0.99
  • System efficiency up to 95%, and up to 98% in ECO mode
  • Very wide input voltage range and 40 to 70 Hz frequency range
  • Flexible battery quantity configuration and intelligent charge management
  • Parallel capability for up to 4 units
  • LCD + LED display and standard RS232 communication, with SNMP, RS485 and dry contact options

Models in This Series

EA906RT, EA9010RT

Technical specifications are based on the manufacturer's (EAST) official datasheet and may vary depending on product version and generation.

Purchase and Consultation

Ista Afagh Energy supplies this series together with capacity-selection consulting, battery sizing for the required backup time, installation and commissioning, and after-sales service. For current pricing and stock availability, add the product to your order basket or contact us.

Technical specifications

BrandEAST
SeriesEA900RT 6-10kVA
Model
ModelsEA906RT, EA9010RT (S = standard model, H = long time model)
CapacityEA906RT: 6 kVA / 6 kW | EA9010RT: 10 kVA / 10 kW
Input
Input wiringSingle-phase three-wire (1Φ + N + PE)
Rated voltage208 / 220 / 230 / 240Vac
Input voltage range90 ~ 176 Vac (linear derating between 30% and 100% load); 176 ~ 288 Vac (no derating)
Rated frequency50 / 60 Hz (auto-sensing)
Frequency range40 ~ 70 Hz
Power factor≥ 0.99
Bypass voltage range- 40% ~ +15% (settable)
Input current THDi≤ 5%
Output
Output wiringSingle-phase (L-N)
Output voltage208 (PF=0.9) / 220 / 230 / 240 Vac
Voltage regulation± 1%
Output frequencySynchronized to bypass in mains mode; 50 / 60Hz ±0.1%Hz in battery mode
WaveformSinusoidal
Output power factor1
Output voltage THDv≤ 1% (linear load); ≤ 4% (non-linear load)
Crest factor3:1
Overload105% ~ 110% for 10 min, 110% ~ 125% for 1 min, 126% ~ 150% for 30 s
Transfer time0 ms
ProtectionsShort-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure
Max. parallel connections4
Battery
Battery DC voltage192 Vdc (192 ~ 240 Vdc settable)
Number of batteriesDefault 16pcs, settable 10 ~ 20 pcs (10 ~ 15pcs linear derating to 50%)
Inbuilt battery (standard model)EA906RT: 12 V / 7 Ah × 16 | EA9010RT: 12 V / 9 Ah × 16
Charging currentStandard model: 1A (default), 1 ~ 5A settable; Long time model: 5 A (default), 1 ~ 5 A settable; 12 A (optional)
Recharge timeStandard model: 90% capacity restored in 8 hours; Long time model: depend on the capacity of battery
Efficiency
Efficiency≥ 94% at 100% load, max. 94.5% at 60% load, ≥ 98% in ECO mode
Display & Communication
DisplayLCD + LED
CommunicationsRS232 (standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation (optional)
Operating Environment
Operating temperature0℃ ~ 40℃
Storage temperature-25℃ ~ 55℃ (without battery)
Relative humidity0 ~ 95% (non-condensing)
Altitude≤ 1000 m, derating 1% for each additional 100 m
IP ratingIP 20
Noise level (at 1 m)≤ 58dB
Dimensions & Weight
Dimensions (W×D×H) mm440×660×176 (S); 440×470×88 (H)
Packaged dimensions (W×D×H) mm555x815x398 (S); 514x608x168 (H)
Net weight (kg)EA906RT: 58 (S), 12 (H) | EA9010RT: 63 (S), 14 (H)
Gross weight (kg)EA906RT: 63 (S), 14 (H) | EA9010RT: 73 (S), 16 (H)