EAST EA900Pro RT UPS (1 kVA – 3 kVA) EAST
EAST EAST Online EA900Pro RT

EAST EA900Pro RT UPS (1 kVA – 3 kVA)

The EAST EA900 Pro RT series is a high-frequency online double-conversion UPS in a rack/tower form factor, rated from 1 to 3 kVA (EA901RT to EA903RT) with a 0.9/1.0 output power factor.
Technology
Online (Double Conversion)
Capacity
1–3 kVA
Phase
1-phase in / 1-phase out
  • High frequency on-line double conversion with DSP control
  • Rack/tower design, 2U height
  • Input PF up to 0.99 (APFC), output power factor 0.9/1.0
  • Wide input voltage range (110 V ~ 300 Vac) and frequency range (40 ~ 70 Hz)
  • Hot-swappable battery
  • Advanced battery management (ABM); 90% capacity restored in 3h
  • LCD + LED display; output voltage, EOD, auto-start, bypass settable via LCD
  • RS232 standard; USB / RS485 / SNMP / dry contacts optional
Price
Request a quote
In stock
Ask on WhatsApp 02128426849
Notify me of a price drop
Security code
Or order via messenger

Your order text is prepared and copied — just send it.

Genuine product After-sales service Nationwide delivery
Share:

Overview EAST EA900Pro RT UPS (1 kVA – 3 kVA)

The EAST EA900 Pro RT series is a high-frequency online double-conversion UPS in a rack/tower form factor, rated from 1 to 3 kVA (EA901RT to EA903RT) with a 0.9/1.0 output power factor. Transfer time from mains to battery is zero, efficiency reaches ≥92% in mains mode and ≥97% in ECO mode, and the batteries are hot-swappable. At 2U high, it is well suited to installation in network racks, server rooms and small data centers.

Key Features of the EA900Pro RT Series

  • High-frequency online double-conversion technology with DSP control
  • Rack/tower design, 2U high
  • Input power factor up to 0.99 (APFC) and output power factor 0.9/1.0
  • Wide input voltage range (110 to 300 Vac) and 40 to 70 Hz frequency range
  • Hot-swappable batteries
  • Advanced battery management (ABM) and fast charging (90% in 3 hours)
  • LCD + LED display with adjustable output voltage, EOD and bypass mode
  • Standard RS232 communication; optional USB, RS485, SNMP and dry contact

Models in This Series

EA901RT, EA902RT, EA903RT

Technical specifications are based on the manufacturer's (EAST) official datasheet and may vary depending on product version and generation.

Purchase and Consultation

Ista Afagh Energy supplies this series together with capacity-selection consulting, battery sizing for the required backup time, installation and commissioning, and after-sales service. For current pricing and stock availability, add the product to your order basket or contact us.

Technical specifications

BrandEAST
SeriesEA900Pro RT
Model
ModelsEA901RT, EA902RT, EA903RT (standard S and long time H models)
CapacityEA901RT: 1kVA / 1kW | EA902RT: 2kVA / 2kW | EA903RT: 3kVA / 3kW
Input
Rated voltage208 / 220 / 230 / 240Vac
Input voltage range110 ~ 176Vac (linear derating between 50% and 100% load); 176 ~ 280Vac (no derating); 280 ~ 300Vac (derating 50%)
Frequency range40 ~ 70Hz (auto-sensing)
Power factor≥0.99
Bypass voltage range-25% ~ +15% (settable)
Input current THDi≤ 6%
Output
Output voltage208 / 220 / 230 / 240Vac (settable via LCD)
Voltage regulation±1%
Output frequency45 ~ 55Hz or 55 ~ 65Hz (synchronized range); 50 / 60Hz ± 0.1Hz (battery mode)
WaveformSinusoidal
Output power factor0.9/1.0
Output voltage THDv≤2% (linear load), ≤5% (non-linear load)
Crest factor3:1
Overload105% ~ 125% for 1min, 125% ~ 150% for 30s, >150% for 300ms
Transfer timeMains mode to battery mode: 0 ms; Inverter mode to bypass mode: 4 ms (typical)
ProtectionsShort-circuit, overload, overtemperature, battery discharge protection and fan testing protection
Battery
Battery DC voltage24V(S/H), 36V(S/H), 48V(S/H), 72V(S/H), 96V(S/H)
Charging currentStandard model: 1A, long time model: 6A
Recharge timeStandard model: 90% capacity restored in 3 hours; Long time model: depend on the capacity of battery
Efficiency
Efficiency (mains mode)EA901RT: ≥90% | EA902RT: ≥91% | EA903RT: ≥92%
Efficiency (battery mode)EA901RT: ≥85% | EA902RT: ≥86% | EA903RT: ≥87%
Efficiency (ECO mode)EA901RT: ≥95% | EA902RT: ≥96% | EA903RT: ≥97%
Display & Communication
DisplayLCD + LED
CommunicationsRS232 (standard), USB / RS485 / dry contacts / SNMP (optional)
Model
StandardsEN 62040-1, EN 62040-2, EN 61000-3-2, EN 61000-3-3, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2, IEC 62040-2, IEC 62040-1, IEC 62040-3
Operating Environment
Operating temperature0℃ ~ 40℃
Storage temperature-25°C ~ 55°C (without batteries)
Relative humidity0 ~ 95% (non-condensing)
Altitude≤ 1000m, derating 1% for each additional 100 m
IP ratingIP 20
Noise level (at 1 m)≤ 50dB
Dimensions & Weight
Dimensions (W×D×H) mm2U rack/tower, 440×338×88 / 440×468×88 / 440×560×88 (varies by battery voltage)
Net weight (kg)EA901RT: 10.6 to 27.2 | EA902RT: 15.5 to 26.8 | EA903RT: 25.6 to 27.2 (varies by battery voltage / model)